Aithon AL20X has been tested to European Standard 13501-1 Reaction to Fire. The system can achieve a Euroclass B-s1 d0 rating on timber and wood derivatives with a minimum thickness of 10mm and a density equal to or greater than 390kg/m³.
Indoor Spreading rate of Aithon AL20X, with no F4X topcoat = 20m² per 5kg – one or two coat application
Outdoor Spreading rate of Aithon AL20X & Indoor with F4X topcoat = 14.29m² per 5kg – one or two coat application
This white, water-based intumescent paint only requires the F4X topseal on external projects.
Not suitable for use on all woods. Please contact us for more details.
Application & storage conditions:
Temperatures should remain above 5°c during drying
Ambient humidity should not exceed 70%
Protect from freezing – Storage temperature: 7 – 30 °C.
Storage & Application Conditions:
Storage temperature must be between 7 and 30°C.
Please ensure that the product is applied and dried in conditions that are warmer than 5°C and that ambient humidity is lower than 70%.
The moisture content of the timber should be checked and must be below 12% before application of the AL20X.
The AL20X basecoat must be completely dry before applying the F4X topseal with the moisture content being checked again and below 12% before application of the F4X topseal.
Application Instructions
FOR FULL INSTRUCTIONS PLEASE ENQUIRE ON 01752 690997 OR SALES@FIREPROOFPAINT.CO.UK
AL20X and F4X can be applied by brush, roller or a spray gun.
Stir the products thoroughly before application.
Clean tools with water and natural detergent.
IMPORTANT INFORMATION ON PURCHASING OF PASSIVE FIRE PROTECTION PRODUCTS NOTICE:
The information displayed about the products on this website is to be used for guidance ONLY, we advise that all customer contact our technical department to obtain a free no obligation specification and quotation before purchasing goods directly from the website.
Products purchased directly from our website without specification will NOT qualify for certification.
Please be aware that any negligence caused by failure to obtain the relevant advice, or availment of our specification and estimation service, will absolve International Passive Fire Ltd from any liability should Passive Fire Protection Products prepared, or used, by the purchaser, or any other parties, result in damage to property or human life, or for any monetary costs incurred due to incorrect usage.