Application Instructions
Ensure that:
The product specification is appropriate for your intended requirements.
The basecoat is fully dried.
The surface finish of the basecoat is suitable for overcoating.
The correct dry film thickness (DFT) of basecoat has been applied before topsealing.
The number of coats of topseal required in accordance with the specification (one or two coats).
The topseal is fully mixed prior to its application.
The number of coats has been determined to suit the specified colour.
The spray equipment is suitable for the correct application of the topseal.
The site conditions are within the specified limits for application of the topseal.
The topseal is stored within the specified conditions.
You are fully conversant with the application instructions prior to applying the topseal.
Only apply the product onto a fully dried System S Basecoat; normally this will be 3-5 days after basecoat application. Dependant upon site conditions, heavy basecoat loadings may require longer drying periods prior to the application of TS815 Topseal.
The surface of the dried basecoat must be clean, free from condensation, grease or other contamination.
Wet film thicknesses:
- Internal – 1 coat at 0.100
- External – 2 coats at 0.200
TS815SAC Topseal can normally be overcoated after 8 hours assuming good air movement and a minimum temperature of 10ºC. For lower temperatures, overnight drying (16 hours) is recommended prior to overcoating.
IMPORTANT INFORMATION ON PURCHASING OF PASSIVE FIRE PROTECTION PRODUCTS NOTICE:
The information displayed about the products on this website is to be used for guidance ONLY, we advise that all customer contact our technical department to obtain a free no obligation specification and quotation before purchasing goods directly from the website.
Products purchased directly from our website without specification will NOT qualify for certification.
Please be aware that any negligence caused by failure to obtain the relevant advice, or availment of our specification and estimation service, will absolve International Passive Fire Ltd from any liability should Passive Fire Protection Products prepared, or used, by the purchaser, or any other parties, result in damage to property or human life, or for any monetary costs incurred due to incorrect usage.